Apply to
testing the performance of insulation resistance between electrical equipment
or wire to ground, to make sure the equipment run normally.
Digital
insulation resistance meter also known as megohm meter, high voltage insulation
resistance tester. This instrument has LCD big screen grey and white backlight
display, data storage, data checking, alarm, automatic shutdown and other
functions.
7、Adopts portable design, easy to operate in the field;
8、High voltage short circuit current ≥1mA, it is an ideal test instrument for measuring insulation resistance such as transformer, generator, high voltage motor, power capacitor, power cable, lightning arrester, etc.
Function |
insulation resistance test, voltage test |
Basic condition |
23℃±5℃,75%rh below |
Rated voltage(V) |
DMG2671: 100V, 250V, 500V,1000V, 2500V, accuracy±3%rdg±5dgt |
DMG2672: 250V,500V, 1000V, 2500V, 5000V, accuracy±3%rdg±5dgt |
|
Test voltage (V) |
Rated voltage×(1±10%) |
Resistance range (GΩ) |
0.01MΩ~200GΩ accuracy±3%rdg±5dgt |
Resistance resolution |
0.01MΩ |
DC voltage range |
0~1000V |
DC voltage resolution |
0.1V |
AC voltage range |
0~750V |
AC voltage resolution |
0.1V |
Output short circuit current |
≥1mA(2500V) |
Measurement of Absorption ratio and polarization index |
Yes |
Power supply |
1.5V(LR14)Alkaline battery *6 |
Back light |
Controllable grey screen backlight, suitable for dark places |
Display mode |
Large LCD display, grey screen backlight |
LCD display size |
108mm×65mm |
Meter size |
240mm (L)×188mm (W)×85mm (H) |
Test wire |
Red HV test wire 1m,black 1m,green 1m |
Data storage |
500 groups,blinking display “FULL” mean full storage |
Data review |
Display “READ” |
Over range display |
Overrange function:display “OL” |
Warning function |
When the measured value exceeds the alarm set value, an alarm prompt will be given |
Power consumption |
STDBY: 40mA Max (Backlight close) |
Turn on with backlight: 43mA Max |
|
measurement:80mA Max (Backlight close) |
|
weight |
1230g (include battery) |
Battery voltage |
Insufficient battery voltage, undervoltage indicator "" display |
Auto power-off |
hut down after 15 minutes without instrument operation |
Insulation resistance |
≥50MΩ (1000V) |
Voltage withstand |
AC3kV 50Hz 1min |
Operating temperature and humidity |
-10℃~+50℃<85%RH |
Storage temperature and humidity |
-15℃~+55℃<90%RH |
standard |
IEC61010-1、IEC1010-2-31、IEC61557-1,5、IEC60529(IP54)、pollution class 2、CAT Ⅲ 300V |
Serial
Number |
Name | Amount |
1 | Mainframe | one |
2 | Test line (one red, one yellow and one black, 1.6m) | one |
3 |
AC
220V power line |
one |
4 | Battery | eight |
5 |
Specification |
one |
6 |
Inspection
Report |
one |
7 |
Certification |
one |